Transformer Equivalent Circuit Calculator
Get every equivalent-circuit parameter of a single-phase or three-phase transformer straight from the short-circuit and open-circuit test readings — plus the single-phase diagram and voltage regulation from no-load to short-circuit.
Equivalent circuit parameters (from the tests)
Referred to Primary
Operating point
About this calculator
A transformer's behavior can be fully characterized, without ever loading it, using two simple tests: the open-circuit (no-load) test and the short-circuit test. Together they give every parameter of the equivalent circuit — the series impedance (Rcc, Xcc) that represents the winding resistance and leakage flux, and the shunt branch (Rfe, Xm) that represents core losses and magnetizing reactance. This calculator does that reduction for you, referred to either side, in either the approximate or exact model, and lets you see the resulting single-phase diagram from no-load all the way to short-circuit.
How to use it
1. Enter the rating
Rated power and both rated voltages. For a three-phase transformer, say whether each rated voltage is line or phase.
2. Enter both tests
Vcc/Icc/Pcc from the short-circuit test and V0/I0/P0 from the open-circuit test, noting which side each was performed on.
3. Pick a model
Approximate (L) for quick regulation estimates, or Exact (T) to solve the full circuit including the magnetizing branch.
4. Move the load slider
0% is the open-circuit condition; the "Short circuit" shortcut sets Zload = 0 (and switches to the Exact model, since Kapp's formula does not hold there).
The formulas
The last line is Kapp's approximate voltage-regulation formula, used by the Approximate (L) model. The Exact (T) model instead solves the full circuit — including the magnetizing branch — as a linear system of phasor equations, with no small-angle approximation.
Worked example
50 kVA, 2400/240 V single-phase transformer
Short-circuit test (primary): Vcc = 48 V, Icc = 20.8 A, Pcc = 617 W → Rcc = 1.426 Ω, Xcc = 1.814 Ω (referred to primary).
Open-circuit test (secondary): V0 = 240 V, I0 = 5.41 A, P0 = 186 W → Rfe = 309.7 Ω, Xm = 44.8 Ω (referred to secondary).
At rated load (100%) and cos φ = 0.8 lagging, both models agree closely: U2 ≈ 235.4 V, a voltage regulation of about 1.9%.
Reading the results
- %Zcc is the nameplate impedance voltage. The lower it is, the smaller the voltage drop under load, but the larger the short-circuit current (roughly 100 / %Zcc times the rated current).
- Regulation is positive for lagging loads and can become negative for leading (capacitive) ones, where the secondary voltage rises above its no-load value.
- Phasor diagram: it is drawn with the same fixed scales for every load (voltages relative to U1, currents relative to 150 % of the rated current), so the vectors grow as you move the slider. A » after a label means the vector is longer than the scale allows and is clipped.
- Referred to: primed quantities (U2', I2') are referred to the primary; when you choose the secondary as reference it is U1' and I1' that carry the prime.